Fronius Primo Installation Instructions Manual

Fronius Primo Installation Instructions Manual

Grid-connected inverter
Hide thumbs Also See for Primo:

Advertisement

/ Perfect Charging / Perfect Welding /
Fronius Primo:
Explanation of symbols and choice
of location
Notes regarding installation and
connection
42,0426,0204,EN 013-04042019
Fronius prints on elemental chlorine free paper (ECF) sourced from certified sustainable forests (FSC).
Solar Energy
Installations instructions
Grid-connected inverter

Advertisement

Table of Contents
loading

Summary of Contents for Fronius Primo

  • Page 1 / Perfect Charging / Perfect Welding / Solar Energy Installations instructions Fronius Primo: Explanation of symbols and choice Grid-connected inverter of location Notes regarding installation and connection 42,0426,0204,EN 013-04042019 Fronius prints on elemental chlorine free paper (ECF) sourced from certified sustainable forests (FSC).
  • Page 3: Table Of Contents

    Connecting aluminium cables ....................... Notes regarding dummy devices ......................Inverter DC connection ......................... Multi MPP tracker inverters - Fronius Primo 3.0 - 8.2 ................Notes regarding the laying of data communication cables ................ Laying data communication cables....................... Notes regarding attaching the inverter to the wall bracket .................
  • Page 5: Explanation Of Symbols

    Explanation of symbols Explanation of DANGER! safety notices Indicates immediate danger. ► If not avoided, death or serious injury will result. WARNING! Indicates a potentially hazardous situation. ► If not avoided, death or serious injury may result. CAUTION! Indicates a situation where damage or injury could occur. ►...
  • Page 6 In order to minimise the heating up of the inverter, do not expose it to di- rect insolation. Install the inverter in a protected location, e.g. in the vicin- ity of the solar modules or beneath the eaves. Can be used at altitudes of up to 4000 m max.
  • Page 7: Explanation Of Symbols - Installation Position

    Explanation of symbols - instal- lation position The inverter is designed to be installed vertically on a vertical wall or pil- lar. The inverter is suitable for horizontal installation. The inverter is suitable for installation on a sloping surface. Do not install the inverter on a sloping surface with its connection sockets facing upwards.
  • Page 8 Do not install the inverter such that it overhangs with its connection sock- ets facing downwards. Do not install the inverter on the ceiling.
  • Page 9: Choice Of Location

    Fronius the installation of components that are not distributed or expressly approved by Froni- Fronius shall not be liable for any damage resulting from such action. No warranty claims will be entertained. Proper use also includes...
  • Page 10 If the inverter is installed in a switch cabinet or a similar sealed area, then forced-air ven- tilation must be provided to ensure adequate heat dissipation If the inverter is to be installed on the outer wall of a cattle shed, maintain a minimum all- round clearance of 2 m between the inverter and all ventilation and other openings in the building.
  • Page 11: Installation Notes

    Installing the in- When mounting the inverter on a mast or a verter on a mast vertical carrier, Fronius recommends the use of a standard mast fixing kit. This kit enables the inverter to be mounted Fronius Primo on round or rectangular masts with various Installation Help cross-sections.
  • Page 12: Notes Regarding Grid Connection

    Notes regarding grid connection Monitoring the To provide the best possible grid monitoring, the resistance in the leads to the AC-side ter- grid minals should be as low as possible. AC terminals Ground conductor / grounding min. 2,5 mm² - max. 16 mm² Phase conductor Neutral conductor Max.
  • Page 13: Grid Connection Of Inverter Or Dummy Device

    Immediately connect the cable end to the terminal IMPORTANT!Repeat the procedure if the cable has been disconnected and is to be re- connected. Grid connection IMPORTANT! To ensure a proper ground connection, all three PE grounding terminals of inverter or must be tightened to the specified torque when the inverter is installed.
  • Page 14: Maximum Fuse Rating On Alternating Current Side

    For this situation, a type A residual-current circuit breaker is generally adequate. However, in certain circumstances, and depending on local factors, the type A residual-current circuit breaker may trip at the wrong time. For this reason, Fronius recommends that a residual-current circuit breaker that is suitable for frequency converters should be used.
  • Page 15: Notes Regarding Dc Connection

    The temperature coefficients on the solar modules data sheet must be observed More exact values for dimensioning the solar modules can be provided by suitable cal- culation programs, like the Fronius Solar.configurator (which can be downloaded from www.fronius.com). NOTE! Before connecting up the solar modules, check that the voltage for the solar mod- ules specified by the manufacturer corresponds to the actual measured voltage.
  • Page 16: Connecting Aluminium Cables

    Connecting alu- The DC-side terminals are suitable for connecting single-wire, round aluminium cables. minium cables Because of the formation of a non-conductive oxide layer due to the reaction of aluminium with air, the following points must be considered when connecting aluminium cables: the reduced rated currents for aluminium cables the connection conditions listed below NOTE!
  • Page 17: Inverter Dc Connection

    - Froni- (MPP trackers) available. These can be connected to an unequal number of solar modules. us Primo 3.0 - 8.2 There are two terminals for DC+ available per MPP tracker. In total there are four terminals for DC-.
  • Page 18 Divide the strings between the two MPP tra- PV 1 cker inputs (DC+1/DC+2). The DC- termi- PV 2 nals can be used however you wish, as they are internally connected. When starting for the first time, set MPP TRACKER 2 to "ON" (this can also be done later in the Basic menu).
  • Page 19: Notes Regarding The Laying Of Data Communication Cables

    To cater for this eventuality, a suitable blan- king cover (42,0405,2020) is available from Fronius as an option. IMPORTANT! Note the following if data communication cables are being introduced into the inverter: depending on the number and cross-section of the data communication cables that are being introduced, take the relevant blanking plugs out of the sealing insert and in- sert the data communication cables.
  • Page 20: Notes Regarding Attaching The Inverter To The Wall Bracket

    Notes regarding attaching the inverter to the wall bracket Attaching the in- The side sections of the housing lid are designed to function as holding and carrying han- verter to the wall dles. bracket NOTE! For safety reasons, the inverter is fitted with a latch that prevents the inverter from being swung into the wall bracket unless the DC main switch is switched off.
  • Page 21: Notes Regarding Software Updates

    Notes regarding software updates Notes regarding If the inverter is supplied with a USB stick, software updates the inverter software must be updated as soon as the inverter has been commissi- oned: Plug the USB stick into the data com- munication area of the inverter Open the Setup menu Select the "USB"...
  • Page 22: Usb Stick As A Data Logger And For Updating Inverter Software

    Only delete all of the files (sys, fld, csv) at one time. DALO.fld log file: A log file for reading the data in the Fronius Solar.access software. Further details on the Fronius Solar.access software can be found in the "DATCOM Details" operating instructions at http://www.fronius.com DATA.csv log file: A log file for reading the data in a spreadsheet program (e.g.: Microsoft®...
  • Page 23: Data Volume And Storage Capacity

    Inverter no. Inverter type (DATCOM code) Logging interval in seconds Energy in watts per second, relative to the logging interval Inductive reactive power Capacitive reactive power Average values during the logging interval (AC voltage, AC current, DC voltage, DC current) Additional information Data volume and A USB stick with a storage capacity of 1 GB can record logging data for roughly seven...
  • Page 24: Suitable Usb Flash Drives

    2.0 Operating Instructions, section "Setting and displaying the menu items", "Viewing and adjusting parameters in the DATCOM menu item"). On the Fronius Eco or Fronius Symo 15.0-3 208, the buffer memory also functions with just a DC supply. Suitable USB...
  • Page 25: Usb Stick For Updating The Inverter Software

    USB stick for up- With the help of the USB stick, end customers can also update the inverter software via the dating the invert- USB item on the SETUP menu: the update file is first saved to the USB stick, from where er software it is then transferred to the inverter.
  • Page 26: Notes Regarding Maintenance

    NOTE! When installed outdoors in a horizontal position: once a year, check that all screw joints are tight! Maintenance and servicing may only be carried out by Fronius-trained service technicians. Cleaning Clean the inverter as required with a damp cloth.
  • Page 27: Serial Number Sticker For Customer Use

    Two serial number stickers are enclosed with the inverter's Installation Instructions: 57 x 20 mm 67 x 20 mm Fronius Inverter These can be affixed by the customer in a Installation visible location of his choosing, e.g. on the front of the inverter or on the Operating Ins- tructions.
  • Page 28 FRONIUS INTERNATIONAL GMBH Vorchdorfer Straße 40, A-4643 Pettenbach, Austria E-Mail: sales@fronius.com www.fronius.com Under www.fronius.com/contact you will find the addresses of all Fronius Sales & Service Partners and locations...