Fronius Ig Plus A 6.0-1 - Fronius IG Plus A 3.0-1 UNI Operating Instructions Manual

Inverter for grid-connected photovoltaic systems
Table of Contents

Advertisement

Fronius IG Plus A
Input data
6.0-1
Recommended PV power
MPP voltage range
Start voltage
Max. input voltage
(at 1000 W/m² / 14 °C in an open circuit)
Nominal input voltage
Nominal input current
Max. input current
Max. array short circuit current
Output data
Nominal output power (P
P
nom
Max. output power
Nominal AC output voltage
Grid voltage tolerance
Operating AC voltage range default,
Adjustment range for voltage,
Voltage trip limit accuracy
Voltage clearing times
Nominal output current
Number of phases
Maximum continuous utility backfeed current *
Synchronization in-rush current *
Maximum output fault current / duration
Nominal output frequency
Operating frequency range
Adjustment range for frequency
Frequency trip limit accuracy
Frequency clearing times
Harmonic distortion
Power factor
(at nominal output power)
*
**
)
nom
at +122 °F (50 °C)
assured by electrical design of the inverter
ind. = inductive; cap. = capacitive
208 V / 240 V / 277 V
at 208 V
at 240 V
at 277 V
at 208 V
at 240 V
at 277 V
1 % of nominal value
at 208 V
at 240 V
at 277 V
0,85 - 1 ind./cap.**
5100 - 6900 Wp
230 - 500 V DC
260 V
600 V DC
390 V
16.5 A
28.1 A
35.1 A
6000 W
6000 W
6000 W
+10 / -12 %
183 - 229 V
211 - 264 V
244 - 305 V
105 - 248 V
121 - 287 V
140 - 324 V
0.016 - 4.25 s
28.8 A AC
25.0 A AC
21.7 A AC
1
0 A
0 A
426 A / 125 μs
60 Hz
59.3 - 60.5 Hz
57.0 - 60.48 Hz
0.05 Hz
0.016 - 300 s
< 3 %
1
153