Refrigerant Shortage - Daikin 2MKS40G2V1B Service Manual

Inverter multi for 2 rooms g-series
Hide thumbs Also See for 2MKS40G2V1B:
Table of Contents

Advertisement

SiBE12-816_D

7.15 Refrigerant Shortage

U0
Remote
Controller
Display
Method of
Refrigerant shortage detection I :
Malfunction
Refrigerant shortage is detected by checking the input current value and the compressor output
frequency. If the refrigerant is short, the input current is smaller than the normal value.
Detection
Refrigerant shortage detection II :
Refrigerant shortage is detected by checking the discharge pipe temperature and the opening of
the electronic expansion valve. If the refrigerant is short, the discharge pipe temperature tends
to rise.
Malfunction
Refrigerant shortage detection I :
Decision
The following conditions continue for 7 minutes.
Conditions
Refrigerant shortage detection II :
The following conditions continue for 80 seconds.
Supposed
Causes
Service Diagnosis
DC current × DC voltage ≤ A × Compressor output frequency + B
Output frequency > C
A
(–)
40 class
2111/256
50 class
4628/256
Opening of the electronic expansion valve ≥ D
Discharge pipe temperature > E × target discharge pipe temperature + F
D
E
(pulse)
(–)
450
255/256
If the error repeats 4 times, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Refrigerant shortage (refrigerant leakage)
Poor compression performance of compressor
Disconnection of the discharge pipe thermistor, indoor or outdoor heat exchanger thermistor,
room or outdoor temperature thermistor
Closed stop valve
Defective electronic expansion valve
B
C
(W)
(Hz)
–361
51
–608
48
F
(°C)
20
Troubleshooting for Outdoor Unit