SiBE12-816_D
6.6

Remote Controller Thermistor Abnormality

CJ
Remote
Controller
Display
Method of
Even if remote controller thermistor is malfunctioning, the system can operate with the system
thermistor.
Malfunction
Malfunction detection is carried out by the temperature detected by the remote controller
Detection
thermistor.
Malfunction
When the remote controller thermistor disconnected or shorted while the unit is running
Decision
Even if the remote controller thermistor is malfunctioning, the system can operate with the
Conditions
system thermistor.
Supposed
Causes
Troubleshooting
Service Diagnosis
Defective thermistor
Broken wire
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn the power supply off once and
then back on.
CJ
Is "
" displayed on
the remote controller?
NO
Troubleshooting for SA Indoor Unit - FFQ Series
YES
Replace the remote
controller.
External factor other than
malfunction. (for example,
noise etc.)
(R11300)
230