4.3

Outdoor Unit

4.3.1 Jumper Settings

(on outdoor unit PCB)
J3
J4
J5
Location of the jumpers
Trial Operation and Field Settings
Jumper
Function
ECONO mode
prohibition setting
Maximum power
input limitation
setting
Improvement of
defrost performance
1) Remove the
2 screws.
Electrical
box cover
Insulation
sheet
Fan motor lead wire
Hook
3) Remove the
electrical box cover
from the hook.
When connected
(factory set)
ECONO operation is
ECONO operation is disabled.
available.
Standard control
The power input is limited to
1700 W. It is recommended for
the areas with circuit breakers
of low-capacity.
Standard control
Reinforced control
(ex. The frequency increases,
the duration time of defrost
lengthens.)
PCB
Field Settings
When cut
Top panel
2) Remove the
screw.
4) Remove the
insulation
sheet.
Notch
Electrical box
PCB
5) Cut the jumper.
(You can cut the jumper
with the PCB mounted.)
(R14361)