Outdoor Unit
Step
7
Disconnect the
connectors [S20],
[S21], [S80].
Disconnect the relay
8
connector for the
compressor.
Disconnect the 2
9
connectors for the
reactor.
10
Release the discharge
pipe thermistor.
277
Procedure
[S20]
[S21]
Discharge pipe thermistor
[S20]: electronic expansion
valve coil for room A
[S80]
(white)
[S21]: electronic expansion
valve coil for room B (red)
[S80]: four way valve coil
(R12532)
(R12533)
(R12534)
Meet the edge of the
thermistor and the clip.
Be careful not to lose the clip
for the thermistor.
(R12535)
SiBE12-816_D
Points
Removal Procedure