INSTALLATION
Installation
Ensure that the installation meets national and regional
regulations. The installation must be approved by an authorized
inspection body.

Supply of combustion air

Supply air from open air must be provided. Combustion air can be
provided directly via a duct from outside, or indirectly via a vent in
the outer wall of the room where the insert is placed. The amount
of combustion air that is used for combustion is approx. 30 m3/h.
Some installation alternatives are shown below. The air duct
connection on the insert has an external diameter of Ø100 mm.
In hot areas, the duct should be insulated with 30 mm mineral
wool covered with a moisture inhibitor for example, aluminium
tape. It is important that the lead-in, between the pipe and the
wall (or floor), is sealed using jointing compound.
A 1 m length of condensation-insulated ducting for combustion air
is available as an accessory.
HK
HK
HK
HK