Troubleshooting
Fault codes
(cont.)
Fault
Const.
Weath.-
code
comp.
on the
display
F0
X
X
F1
X
X
F2
X
X
F3
X
X
F4
X
X
F7
X
X
F8
X
X
80
System char-
Cause
acteristics
Burner
Internal fault
blocked
Burner in a
Flue gas
fault state
temperature
limiter has
responded
Burner in a
The tem-
fault state
perature lim-
iter has
responded
Burner in a
Flame signal
fault state
is already
present at
burner start
Burner in a
No flame sig-
fault state
nal.
Burner
Differential
blocked
pressure
sensor faulty
Burner in a
The fuel
fault state
valve closes
too late
Measures
Replace the con-
trol unit
Check flue gas
path/route; press
"E"
Check the heating
system fill level,
the circulation
pump, the tem-
perature limiter
and interconnect-
ing cables/leads;
vent the system;
press "E"
Check the ionisa-
tion electrode and
interconnecting
lead; press "E"
Check the ionisa-
tion electrode,
ignition, ignition
module, intercon-
necting cables/
leads, gas pres-
sure, gas train
and the ionisation
current;
press "E"
Check differential
pressure sensor
and lead
Check the gas
train and both
control paths;
press "E"