Viessmann VITODENS 333-F WS3A Service Instructions Manual page 78

Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Fault
Const.
Weath.-
code
comp.
on the
display
C5
X
X
C6
X
C7
X
X
Cd
X
X
CE
X
X
CF
X
78
System char-
Cause
acteristics
Control mode,
Communica-
max. pump
tion error
speed
variable
speed inter-
nal pump
Control mode,
Communica-
max. pump
tion fault, ex-
speed
ternal vari-
able speed
heating cir-
cuit pump,
heating
circuit M2
Control mode,
Communica-
max. pump
tion fault, ex-
speed
ternal vari-
able speed
heating cir-
cuit pump,
heating
circuit A1
Control mode
Communica-
tion fault
Vitocom 100
(KM BUS)
Control mode
Communica-
tion fault,
ext. exten-
sion
Control mode
Communica-
tion fault,
LON com-
munication
module
Measures
Check coding ad-
dress "30" set-
tings; check the
DIP switch set-
tings in the pump
wiring chamber:
Switch 1: OFF,
switch 2: ON
Check coding ad-
dress "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring chamber:
Switch 1: OFF,
switch 2: ON
Check coding ad-
dress "E5" set-
tings; check the
DIP switch set-
tings in the pump
wiring chamber:
Switch 1: ON,
Switch 2: OFF
Check connec-
tions, Vitocom 100
and coding ad-
dress "95"
Check connec-
tions and coding
address "2E"
Replace the LON
communication
module

Hide quick links:

Advertisement

Table of Contents
loading