Viessmann VITODENS 333-F WS3A Service Instructions Manual page 48

Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
DHW
56:0
Set DHW temperature
adjustable from 10 to
60 °C
58:0
Without auxiliary func-
tion for DHW heating
63:0
No default interval for
auxiliary function for
DHW heating (only for
constant temperature
control units)
65:...
Information regarding
the type of diverter
valve; do not adjust.
67:40
With the Vitosolic:
Third set DHW tem-
perature = 40 °C
6C:100
Set speed; internal cir-
culation pump with
DHW heating 100 %
48
Possible change
56:1
Set DHW temperature
adjustable from 10 to
above 60 °C
Note
Maximum value subject
to boiler coding card
Observe the maximum
permissible DHW tem-
perature
58:10
Input of a second set
to
DHW value, adjustable
58:60
from 10 to 60 °C (observe
the coding addresses
"56" and "63")
63:1
Auxiliary function for
DHW heating, 1 x daily
63:2
Every 2 days to every 14
to
days
63:14
63:15
2 x daily
65:0
Without diverter valve
65:1
Diverter valve by
Viessmann
65:2
Diverter valve by Wilo
65:3
Diverter valve by Grund-
fos
67:0
Without third set DHW
temperature
67:1
Third set DHW tempera-
to
ture adjustable from 1 to
67:60
60 °C (subject to the set-
ting of coding address
"56")
6C:0
Set speed adjustable
to
from 0 to 100 %
6C:100