Code 2
(cont.)
Coding in the delivered condition
Heating circuit with mixer M2
F1:0
Screed drying function
disabled (only for
weather-compensated
control units).
Possible change
F1:1
Screed drying function
to
adjustable in accordance
F1:5
with five optional tem-
perature/time profiles
(see page 101)
Note
Observe the screed sup-
plier's instructions.
Observe DIN 4725 2.
The report to be provided
by the heating contractor
must contain the follow-
ing heat-up details:
Heat-up data with
respective flow tem-
peratures
Max. flow temperature
achieved
Operating condition
and outside tempera-
ture during handover
The function continues
after power failure or
after the control unit has
been switched OFF.
Heating program "Heat-
ing and DHW" will be
started after the screed
drying function has been
terminated or if the ad-
dress is manually set to
0.
F1:6
Constant flow tempera-
to
ture 20 °C
F1:15
Coding
61