Setting the maximum output

Note
You can limit the maximum output for heating operation. The limit is set via the
modulation range.
1. Start the boiler.
2. K + F
press simultaneously:
"100" flashes (equals
100% of rated output)
and "A" is displayed.
On weather-compen-
sated control units, the
display additionally
shows "Max.heating
output".
a/b
press for the required
value in % of rated output
as max. output.
d
to confirm.
16
(cont.)
Measures
Do not start the boiler. Notify your
mains gas or LPG supplier.
Start the boiler.
Install a separate gas pressure gover-
nor upstream of the system and regu-
late the inlet pressure to 20 mbar for
natural gas or 50 mbar for LPG. Notify
your mains gas or LPG supplier.
3. Record the setting for the maxi-
mum output on the additional type
plate supplied with the "technical
documentation". Affix the type
plate next to the type plate on top
of the boiler.