Further details regarding the individual steps
Setting the maximum output
You can limit the maximum output for heating operation. The limit is set via the
modulation range.
Note
The value to be entered is the approximate percentage of the max. rated output:
100 % corresponds to 29 kW rated output.
1. Start the boiler.
2. K + F
press simultaneously:
"100" flashes (equals
29 kW output) and "A"
is displayed.
On weather-compen-
sated control units, the
display additionally
shows "Max. output".
a/b
for the required output
("34" equals 10.5 kW out-
put).
d
to confirm.
Commissioning, inspection, maintenance
(cont.)
3. Record the setting for the maxi-
mum output on the additional type
plate supplied with the "technical
documentation". Affix the type
plate next to the type plate on top
of the boiler.
29