code display and
var. code
meaning
symbol
I89
Mn
1001Hex
end of cylinder life
EU
2001Hex
cylinder full
EC
1002Hex
high conductivity
E3
-
2002Hex
failed connection of
modulating signal
SU
2040Hex
serial disconnected
Pre/Cln -
cylinder cleaning
started signal
dr
-
cylinder drain
activated
dr / TOT -
complete drain due
to inactivity
AF
antifoam active
Press ESC once to mute the buzzer, press ESC a second time to reset the alarm.
(*) Quick fl ash: 0.2 seconds ON and 0.2 seconds OFF
Slow fl ash: 1 second ON and 1 second OFF
causes
solution
the cylinder has exceeded
the limit of 2000 hours,
replace the cylinder
excessive water
with the machine off :
level when unit
1. check for any leaks from
producing steam
the fi ll electrovalve or the
condensate return
pipe
2. check that the level
sensors are clean
total shut-down pipe
2. check that the level
sensors are clean
total shut-down
high supply water
1. check water
conductivity
conductivity
2. if the problem persists,
change the
source of supply water or
install a
suitable treatment system
(demineralisation, even
partial).
N.B.: the problem will not
be resolved
by softening the supply
water.
Cable interrupted
check the reference signal
/ disconnected
in 4 to 20 mA or 2 to 10V
/ improperly
mode)
connected.
21
reset (press) alarm relay
eff ect
activation
reset hour
yes
humidifi cation
counter
stopped
AUTO
no
signal only
AUTO
no (b5)
signal only
yes (b6)
humid. stopped
AUTO
yes
humidifi cation
stopped
AUTO
--
--
--
--
--
--
--
--
--
--
--
"UE BASIC" +0300042EE - rel. 1.0 - 02.12.2009
ENG
red LED signal
on board (*)
(if terminal
not
connected)
8 fast fl ashes
8 slow fl ashes
5 fast fl ashes
7 slow fl ashes
2 slow fl ashes
none
none
(both codes
alternate on
display)
none
Need help?
Do you have a question about the humiSteam Basic and is the answer not in the manual?