Technical Data - Kingspan SC100 Installation And Operating Instructions Manual

Temperature difference controller
Table of Contents

Advertisement

13

Technical data

Temperature difference controller
Rated voltage
(system voltage)
Max. own consumption
Inputs
Outputs
Number of pre-defined hydraulic
schemes
Ingress protection
Protection class
Permitted ambient temperature
Display
Dimensions L x W x H [mm]
Software class
Type of action
Type of fastening for permanently con-
nected cables
Intended transport condition
Degree of pollution
Ball pressure test temperature
overvoltage category
13.1
Performance data
Output
Power
R1
50 W (30 VAC)/15 W (115 VAC)
R
800 W (30 VAC)/400 W (115 VAC)
DANGER
Risk of death by electrocution!
Fuses may only be changed after disconnection from the power supply,
and by trained professional personnel!
48
30 VAC, 50 Hz
[optional 115 VAC, 60 Hz]
≤ 4 W
4
T1 - T4: temperature recording (Pt1000)

R1: TRIAC output for RPM control,
max. switching current 1.1 A AC
R: relay switched output, max. switching current 3.47 AAC
4
IP 0/DIN 40050
I
0 to +45 °C
Animated graphic LCD with backlighting
170 x 170 x 46
A
Type 1B
Type X
No information

850 °C
Class II (500 V)
Fuse
Internal fuse: 1.6 A T, 50 V or
T 1.6 A H 50 V (Littelfuse: 1501.6)
Internal fuse: 4 A T, 50 V or
T 4 A H 50 V (Littelfuse: 15004)
78.138 | 08.1