4.3.2
Connecting the cables
If a protective conductor is provided or required for pumps/valves,
connect it to the corresponding terminals of the controller. When
connecting the protective conductor, observe the following points:
Make sure that the protective conductor is also connected to the
-
controller's mains supply side.
Each terminal may only be connected to a single connecting wire
-
(max. .5 mm
).

The terminal screws are approved for connection of cables as fol-
lows:
single wire (solid): ≤ 2.5 mm²
-
fine strand (with core end sleeves): ≤ 1.5 mm²
-
Only use the original temperature sensors (Pt1000) that are
approved for use with the controller.
Observe the following points:
The polarity of the temperature sensor contacts is not important.
-
Do not lay sensor cables close to power cables (minimum sepa-
-
ration: 100 mm).
If inductive effects are expected, e.g. from power cables,
-
overhead wires, transformer substations, radio and television
devices, amateur radio stations, microwave devices, etc., the
sensor cables must be adequately screened.
Sensor cables may be extended to a maximum length of 100 m.
-
If adding extensions to sensor cables, select the following cable
cross sections:
0.75 mm
up to 50 m long

-
1.5 mm
up to 100 m long

-
Connect the cables in accordance with the terminal diagram (see
chapters 4.5 and 7.1).
4.4

Dismantling

DANGER
Risk of death by electrocution!
Remove the controller from the power supply before dismantling it.
To dismantle the controller, follow the assembly instructions in the
reverse order.