66
Installation and User's Guide
8/11k VA 1Phase
N/A
(4) C19 + Terminal blocks
6.8 x 13.2 x 5.1 in. / 172 x 336 x 130 mm
Minimum rack depth for UPS with MBP: 900mm (35.4 inches)
13.7 / 6.2
Nominal voltage
200 - 240 V ~
Frequency
50/60 Hz
Input nominal
50A
current
Maximal power
11000 VA
Standards (HotSwap MBP used with UPS)
IEC/EN 62040-1 /
Safety
Ed.1: 2008. UL 1778
th
4
EMC
IEC 62040-2 / Ed.2:
2005. EN 62040-2 /
Ed.2: 2006. FCC part
15 Class A
Performance
IEC/EN 62040-3 / Ed.2.0: 2011
ESD
IEC 61000-4-2 : level 3
Radiated field
IEC 61000-4-3 : level 3
EFT
IEC 61000-4-4 : level 4
Fast transients
IEC 61000-4-5 : level 4
Electromagnetic field IEC 61000-4-6 : level 3
Conducted magnetic
IEC 61000-4-8 : level 4
field
cULus Listed / CE
Operating
0 to 40°C (32 to 104°F)
temperature
Storage temperature
-15 to 60°C (5 to 140°F)
Transit temperature
-25 to 55°C (-13 to 130°F)
Humidity
0 to 95% no condensing
Up to 3,000 meters (9,843 ft) above sea level with 10% derating per
Operation Altitude
1000m
Transit Altitude
Up to 10,000 meters (32,808 ft) above sea level
MBP11Ki
Terminal Blocks
Output
Overall dimensions D x W x H
Weight (lb / kg)
12.1 / 5.5
Performance
IEC/EN 62040-1 / Ed.1: 2008
edition
IEC 62040-2 / Ed.2: 2005 EN 62040-2 / Ed.2:
2006
Marking
CE
Environment
8/11k VA 3Phase
350 - 430 V ~

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rt11.0va