Shutting Down The Ups; Ups Start-Up With Hotswap Mbp - Lenovo RT8.0kVA Installation And User Manual

6u rack or tower ups
Hide thumbs Also See for RT8.0kVA:
Table of Contents

Advertisement

Procedure
1. Press the power (
2. Check the UPS front panel display for active alarms or notices. Resolve any
3. Check the UPS status from the front panel to view the active alarms. Correct

Shutting down the UPS

About this task
To shut down the UPS:
Procedure
1. Press the
2. If desired, set the upstream circuit breaker (not provided) to the "O" (off)

UPS start-up with HotSwap MBP

About this task
Note: Verify that the total equipment ratings do not exceed the UPS capacity to
prevent an overload alarm.
Procedure
38
Installation and User's Guide
) button on the UPS front panel until the UPS front panel
display illuminates and shows a status of "UPS starting...".
The UPS cycles through Standby mode to Battery mode. The
illuminates solid. The UPS supplies power to your equipment using batteries.
active alarms before continuing. See the Troubleshooting section.
the alarms and restart if necessary.
button on the UPS front panel. The UPS goes into Standby mode.
position to switch off the utility power. The UPS turns off.
1. Check that the UPS is correctly connected to the HotSwap MBP (see
"HotSwap MBP connection" on page 30).
2. Verify that the MBP terminal blocks are connected to the normal AC source
and, if so wired, to the Bypass AC source.
3. Check that the MBP's manual Bypass switch is set to the Bypass position.
4. Set the upstream circuit breaker (not provided) to the I position (on) to switch
on the utility power, and set the Bypass source upstream circuit breaker (not
provided) to the I position (on) to switch on the Bypass power.
5. Verify that the Bypass mode red light on the MBP goes on, indicating that the
load is now powered by the normal AC source the or Bypass AC source.
6. Set the MBP's Normal AC source switch and Bypass AC source switch (if
present) to the I position.
7. Verify that the UPS is correctly powered (the UPS display panel illuminates).
8. Press the UPS On button to start the UPS.
9. Select Control > Go to Bypass (Bypass LED should be On).
indicator