10. Punch the Input and Output knockouts of the UPS I/O terminal block (TB)
11. Insert the conduits
12. Connect the wires of the conduit with blue color coding
13. Connect the MBP detection cable
14. Put back and secure the I/O terminal blocks cover of the UPS.
15. Remove the top cover
16. Punch the knockouts of MBP I/O cover
17. Insert the Normal AC source cable through the cable gland (or a conduit
18. Connect the wires to the Normal AC source (Input) terminal blocks of MBP.
19. Insert the Output cable through the cable gland (or a conduit through the
20. Connect the wires to the Output terminal blocks of MBP.
21. Put back the MBP I/O cover
22. Put back the top cover
23. Tighten the cable glands (if used instead of conduit fittings).
32
Installation and User's Guide
cover and insert the 2 provided conduit fittings inside.
fittings of the UPS I/O TB cover, following color coding on the conduits and
the UPS I/O TB cover: blue for UPS Input; red for UPS Output. Do not
remove the UPS Input Bypass jumper inside the UPS I/O TB cover.
AC SOURCE terminal blocks of the UPS, and the wires of the conduit with
red color coding
to the OUTPUT terminal blocks.
Note: Refer to "Access to terminal blocks" on page 27 for more information
about terminal-block connections.
screws.
conduit fittings) inside.
through the conduit fitting).
conduit fitting).
casing.
screws.
and
through the previously mounted conduit
to the specific UPS connector.
of the MBP I/O cover
and insert cable glands of UPS (or
and secure it with 4 screws on the MBP
of the MBP I/O cover
to the NORMAL
after removing the 3
and secure it with 3