Chapter 4. Power cables connection

CAUTION:
This product might be equipped with a hard-wired power cable. Ensure that a
licensed electrician performs the installation per the national electrical code.
(C022)
Important: This connection must be carried out by qualified electrical personnel.
Before carrying out any connection, check that the upstream protection devices
(Normal AC source and Bypass AC source) are open "O" (off).
Always connect the ground wire first.
Important: Before connecting the HotSwap MBP to the UPS, make sure the UPS
has been properly shut down.
Always connect the ground wire first.

Access to terminal blocks

Procedure
1. Remove the terminal blocks cover (one screw).
2. Punch the knockouts and insert the cables/conduits inside.
© Copyright Lenovo 2015
Important: High leakage current: An earth connection is essential before
connecting to the power supply.
27