Class 4 Status Codes - Fronius Primo 3.0-1 Operating Instructions Manual

Grid-connected inverter
Hide thumbs Also See for Primo 3.0-1:
Table of Contents

Advertisement

Available languages

Available languages

Class 4 status
Some of the class 4 status codes necessitate intervention by a Fronius-trained service en-
codes
gineer.
Code
Description
No communication with power
401
stage set possible
Power stage set temperature
406
sensor faulty
Internal temperature sensor
407
faulty
DC feeding into the grid detect-
408
ed
Fixed voltage mode has been
selected instead of MPP volt-
412
age mode, and the fixed volt-
age has been set to too low or
too high a value.
Safety cut-out via option card
415
or RECERBO has triggered
No communication possible
416
between power stage set and
control system.
417
Hardware ID problem
419
Unique ID conflict
421
HID range error
No communication possible
425
with the power stage set
426 -
Possible hardware fault
428
431
Software problem
436
Functional incompatibility (one
or more PC boards in the in-
verter are not compatible with
each other, e.g. after a PC
board has been replaced)
437
Power stage set problem
Functional incompatibility (one
or more PC boards in the in-
438
verter are not compatible with
each other, e.g. after a PC
board has been replaced)
Intermediate circuit voltage too
443
low or asymmetric
Behaviour
The inverter will automatically
attempt to connect again and,
if possible, will resume feeding
energy into the grid
-
The inverter is not feeding any
energy into the grid.
The inverter will automatically
attempt to connect again and,
if possible, will resume feeding
energy into the grid
The inverter is not feeding any
energy into the grid.
The inverter will automatically
attempt to connect again and,
if possible, will resume feeding
energy into the grid
The inverter will automatically
attempt to connect again and,
if possible, will resume feeding
energy into the grid
The inverter is not feeding any
energy into the grid.
Remedy
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
If this status code keeps recur-
ring, contact your system engi-
neer
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
Carry out an AC reset (switch
the automatic circuit breaker
off and on); update inverter
firmware;
if this status code is displayed
all the time: notify a Fronius-
trained service engineer
Update the inverter firmware;
if the status code is displayed
all the time: notify a Fronius-
trained service engineer
Update the inverter firmware;
if the status code is displayed
all the time: notify a Fronius-
trained service engineer
If the status code is displayed
all the time: notify a Fronius-
trained service engineer
45

Advertisement

Table of Contents
loading

Table of Contents