To Change Dhw High Limit Setpoint - Ace Heating Solutions Atlas A050 Operating And Maintenance Manual

Table of Contents

Advertisement

x
Select Disable to disable DHW loop high limit
This parameter enables or disables the DHW high limit function. It must be disabled when the DHW input is used as a
switch to indicate DHW demand.

5-6.2 To Change DHW High Limit Setpoint

Configure
High Limits
x
Type in desired temperature between 32 F and 240 F (0 C and 115 C)
If the DHW temperature reaches the value given by this parameter then a response will occur.
5-6.3 To Change Outlet High Limit Setpoint
Configure
High Limits
(Default: 240 F for H and 200 F for HLW)
x
Type in desired temperature between 32 F and 240 F (0 C and 115 C)
If the outlet temperature reaches the value given by this parameter, a response will occur.
5-6.4 To Change DHW High Limit Response
Configure
High Limits
x
Select Recycle & Hold for DHW loop high limit response
x
Select Lockout for DHW loop high limit response
If Recycle & Hold is selected then the burner control recycles and holds until the DHW temperature is falls below the
DHW high limit setpoint minus 5F.
5-7 Stack Limit Related Configuration
5-7.1 To Enable Or Disable Stack Limit
Configure
Stack Limit
x
Select Enable Dual Safety sensor to enable Stack limit
x
Select Disable to disable Stack limit
This parameter enables or disables the entire stack temperature limit function.
5-7.2 To Change Stack Limit Delay
Configure
Stack Limit
x
Type in desired time between 0 to 5 minutes
This parameter provides the delay time for the Stack limit.
5-7.3 To Change Stack Limit Response
Configure
Stack Limit
x
Select Lockout to lockout in event of Stack limit
x
Select Recycle & delay to recycle and delay in event of Stack limit
For Recycle and Delay, the burner control recycles and holds while waiting for a delay (see the Stack Limit Delay
parameter) to expire, and after the delay it tries again.
5-7.4 To Change Stack Limit Setpoint
Configure
Stack Limit
x
Type in desired temperature between 32 F and 266 F (0 C and 130 C)
If the stack temperature exceeds the temperature given by this parameter then the response defined for the Stack
Limit Response parameter will occur. As the temperature approaches this limit, the Stepped Modulation Limiting
function is active.
DHW High Limit Setpoint Textbox (Default: 200 F)
Outlet High Limit Setpoint Textbox
DHW High Limit Response Textbox (Default: Lockout)
Stack Limit Textbox (Default: Disable)
Stack Limit Delay Textbox (Default: 5m0s)
Stack Limit Response Textbox (Default: Recycle & Delay)
Stack Limit Setpoint Textbox (Default: No Valve)
77
Rev 2.1