Lead Lag Master Configuration Parameters; Lead Lag Master Configuration Parameters Advanced Settings - Ace Heating Solutions Atlas A050 Operating And Maintenance Manual

Table of Contents

Advertisement

4-32 Lead Lag Master Configuration Parameters

Table 4.19 displays Lead Lag Master configuration parameters.
Refer to 5-14 LEAD LAG MASTER CONFIGURATION for Lead Lag Master parameter programming.
Parameter
Master enabled
LL CH setpoint
LL CH TOD setpoint
Modbus port
Modbus address

4-33 Lead Lag Master Configuration Parameters Advanced Settings

Following tables display Advanced Settings for Lead Lag Master configuration parameters.
Refer to 5-15 to 5-23 ADVANCED LEAD LAG CONFIGURATION for Lead Lag Master parameter programming.
Parameter
Modulation backup sensor
Off hysteresis
On hysteresis
Hysteresis step time
P-gain
I-gain
D-gain
Parameter
Demand switch
Setpoint source
Time of day setpoint
4 mA water temperature
Table 4.18 – Lead Lag Slave Configuration Parameters
Disabled: The master function is disabled.
Enabled: Enable the lead lag master.
This parameter provides the setpoint used during LL CH
demand.
This setpoint is used when the time-of-day switch is on.
MB1, MB2 or No Port
Modbus port use for lead lag operation.
0-250
Modbus address used to communicate with the unit. This
address number must be unique for each burner on the
network.
Table 4.19 – Lead Lag Master Configuration Parameters
Select backup LL modulation sensor
Disable: No backup sensor will be used.
Lead outlet: Outlet temperature of the lead boiler will be
used as the backup sensor.
Outlet average: Average of the outlet temperatures of all
slave boilers that are firing will be used as a backup.
Differential above setpoint when Last LL stage boiler is
turned off
2 °F to 30 °F (1 °C to 16 °C)
Differential below setpoint when First LL stage boiler is
turned on
2 °F to 30 °F (1 °C to 16 °C)
Time between hysteresis step changes
(0=Disable hysteresis stepping)
Proportional term of PID
0-400
Integral term of PID
0-400
Differential term of PID
0-400
Table 4.20 – Lead Lag Advanced Setting: Modulation Parameters
STAT terminal: the STAT input in the On condition
creates lead lag demand and it also must be on for
burner demand to exist; if it is off there is no demand.
Disable: Demand switch input is not used.
Local: Local setpoint is used as lead lag setpoint.
Modbus: Setpoint source from modbus communication
4-20mA: Setpoint is determined by the 4-20mA remote
input. Two parameters that determine the temperature at
the extremes (20mA and 4mA). If the 4-20mA signal is
invalid, then the setpoint source reverts to Local until the
4-20mA signal is stable again.
Setpoint when Time Of Day switch is on
32 °F to 240 °F (0 °C to 115 °C)
This setpoint is used when the time-of-day switch is on
If the Outdoor Reset function is active then this setpoint
provides one coordinate for the shifted outdoor reset
curve.
-40 to 266F (-40 to 130C)
This parameter provides the temperature for the
interpolation of 4-20mA curve. This value determines the
minimum possible value for the setpoint.
Comment
Comment
Comment
62
Password
Installer
Installer
Installer
Installer
Installer
Password
Installer
Installer
Installer
Installer
Installer
Installer
Installer
Password
Installer
Installer
Installer
Installer
Rev 2.1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents