4-21 Modulation Configuration Parameters

Table 4.8 displays Modulation configuration parameters.
Refer to 5-4 MODULATION RELATED CONFIGURATION for Modulation parameter programming.
Parameter
CH maximum modulation rate
DHW maximum modulation rate
Minimum modulation rate
CH forced rate time
CH forced rate
DHW forced rate time
DHW forced rate
CH slow start enable
DHW slow start enable
Slow start degrees
Slow Start Ramp
0-10/4-20 mA Output hysteresis
4-20 mA input hysteresis

4-22 Pump Configuration Parameters

Table 4.9 displays Pump configuration parameters.
Refer to 5-5 PUMP CONTROL RELATED CONFIGURATION for Pump parameter programming.
Table 4.7 – Domestic Hot Water (DHW) Configuration Parameters
RPM
These parameters provide the limits of fan speed during
modulation.
RPM
These parameters provide the limits of fan speed during
modulation.
RPM
0-600 seconds
This parameter determines the duration of the forced rate
period, when firing for CH or LL demand. If it is set to zero
then this forced rate period is disabled.
RPM
This parameter provides the firing rate during the CH
forced rate time. It is also the initial rate
for the CH slow start period.
0-600 seconds
This parameter determines the duration of the forced rate
period, when firing for DHW
demand. If it is set to zero then this forced rate period is
disabled.
RPM
This parameter provides the firing rate during the DHW
forced rate time. It is also the initial rate for the DHW slow
start period.
Disable or Enable CH slow start
This parameter enables or disables the slow start limit
function for CH and LL demand sources. It uses the CH
forced rate parameter as the starting point for the slow
start. If the forced rate parameter is invalid or zero and
slow start is enabled, then the slow start function does not
occur and an alert is issued.
Disable or Enable DHW slow start
This parameter enables or disables the slow start limit
function for DHW demand source. It uses the DHW
forced rate parameter as the starting point for the slow
start. If this forced rate parameter is invalid or zero and
slow start is enabled, then the slow start function does not
occur and an alert is issued.
32 °F to 180 °F (0 °C to 100 °C)
If slow start limiting is enabled and the outlet temperature
is less than the temperature provided by subtracting this
number of degrees from the setpoint, then slow start rate
limiting is effective. Whenever the outlet temperature is
above this value, slow start limiting has no effect.
RPM /minute
When slow start limiting is effective, the modulation rate
will increase no more than the amount per minute given
by this parameter.
Value selects the amount of error (proportional error)
needed to reverse direction.
There is no resistance to change in the same direction as
the last change, but to reverse directions; the input
change must exceed the value provided here.
Table 4.8 – Modulation Configuration Parameter
Comment
57
Password
Installer
Installer
Read Only
Installer
Installer
Installer
Installer
Installer
Installer
Installer
Installer
Installer
Installer
Rev 2.1