5-3.10 To Change DHW Loop P-I-D Parameters

Configure
DHW – Domestic Hot Water Configuration
Configure
DHW – Domestic Hot Water Configuration
Configure
DHW – Domestic Hot Water Configuration
x
Type in desired number between 0 to 400
P gain applied to the proportional term of the PID equation for the DHW loop.
I gain applied to the Integral term of the PID equation for the DHW loop.
D gain applied to the Differential term of the PID equation for the DHW loop.
5-3.11 To Change DHW Modulation Sensor
Configure
DHW – Domestic Hot Water Configuration
(DHW Mode Default: DHW Sensor, Com Mode Default: Outlet Sensor (S1))
x
Select DHW sensor for DHW modulation sensor
x
Select Outlet sensor for DHW modulation sensor
x
Select Inlet sensor for DHW modulation sensor
x
Select Auto DHW (S6) of Inlet (S1) for Inlet modulation sensor when DHW switch is enabled
x
Select Auto DHW (S6) of Outlet (S1) for outlet modulation sensor when DHW switch is enabled
5-3.12 To Change DHW Loop Priority Versus LL
Configure
DHW – Domestic Hot Water Configuration
x
Select LL>DHW for no priority over LL loop
x
Select DHW>LL for priority over LL loop
This parameters determines the priority of DHW vs. the LL call-for heat, when both of these are enabled and active. (If
DHW has a lower priority, it may be boosted to the highest priority temporarily via the DHW Priority Time parameter.)
5-4 Modulation Related Configuration
5-4.1 To Change CH Loop Maximum Modulation Rate
Configure
Modulation Configuration
(Default: Varies based on model)
x
Type in RPM rate between light off rate and maximum modulation rate
Provides the upper limit of modulation when firing for CH or LL slave mode.
5-4.2 To Change DHW Loop Maximum Modulation Rate
Configure
Modulation Configuration
(Default: Varies based on model)
x
Type in RPM rate between light off rate and maximum modulation rate
Provides the upper limit of modulation when firing for DHW.
5-4.3 To Change CH Loop Forced Rate Time
Configure
Modulation Configuration
x
Type in desired time between 0 to 5 minutes
For CH demand, if the CH forced rate time is non-zero, then the firing rate will be held at the rate specified here during
that time. This parameter is also needed as the starting point for Slow State, even if the forced rate time is zero.
5-4.4 To Change CH Loop Forced Rate
Configure
Modulation Configuration
x
Type in RPM rate between light off rate and maximum modulation rate
For CH demand, if this time is non-zero then, upon entry to Run, the firing rate will be held at the CH forced rate.
P-Gain Textbox (Default: 50)
I-Gain Textbox (Default: 50)
D-Gain Textbox (Default: 0)
Modulation Sensor Textbox
DHW Priority vs Lead Lag Textbox (Default: DHW>LL)
CH Maximum Modulation Rate Textbox
DHW Maximum Modulation Rate Textbox
CH Forced Rate Time Textbox (Default: 0m10s)
CH Forced Rate Textbox (Default: Varies based on model)