Ace Heating Solutions Atlas A050 Operating And Maintenance Manual page 105

Table of Contents

Advertisement

152
Combustion pressure ON
153
Combustion Pressure Off
154
Purge Fan switch On
155
Purge fan switch OFF
156
Combustion pressure and Flame ON
157
Combustion pressure and Flame OFF
158
Main valve ON
159
Main valve OFF
160
Ignition ON
161
Ignition OFF
162
Pilot valve ON
163
Pilot valve OFF
164
Block intake ON
165
Block intake OFF
172
Main relay feedback Incorrect
173
Pilot relay feedback incorrect
174
Safety relay feedback incorrect
175
Safety relay open
176
Main relay ON at safe start check
177
Pilot relay ON at safe start check
178
Safety relay ON at safe start check
184
Invalid BLOWER/ HSI output setting
185
Invalid Delta T limit enable setting
186
Invalid Delta T limit response setting
187
Invalid DHW high limit enable setting
188
Invalid DHW high limit response
Setting
189
Invalid Flame sensor type setting
190
Invalid interrupted air switch enable Setting
191
Invalid interrupted air switch start check enable
setting
192
Invalid igniter on during setting
193
Invalid ignite failure delay setting
194
Invalid ignite failure response setting
195
Invalid ignite failure retries setting
196
Invalid ignition source setting
197
Invalid interlock open response setting
198
Invalid interlock start check setting
199
Invalid LCI enable setting
200
Invalid light off rate setting
201
Invalid light off rate proving setting
202
Invalid Main Flame Establishing Period time
setting
203
Invalid MFEP flame failure response setting
204
Invalid NTC sensor type setting
205
Invalid Outlet high limit response setting
206
Invalid Pilot Flame Establishing Period setting
207
Invalid PII enable setting
208
Invalid pilot test hold setting
2. If fault repeats, consult factory
1. Check wiring and correct any errors.
2. Inspect the Combustion Pressure Switch to make sure it is
working correctly.
3. Reset and sequence the relay module.
4. During STANDBY and PREPURGE, measure the voltage
between J6 terminal 5 and L2 (N). Supply voltage should be
present. If not, the lockout switch is defective and needs
replacing.
5. If the fault persists, replace the relay module.
1. Purge fan switch is on when it should be off.
2. 3. Inspect the Purge Fan switch J6 terminal 3 and its
connections. Make sure the switch is working correctly and is
not jumpered or welded.
4. Reset and sequence the relay module.
5. If the fault persists, consult factory.
1. Check that flame is not present in the combustion
chamber. Correct any errors.
2. Make sure that the flame detector is wired to the correct
terminal.
3. Make sure the G wires are protected from stray noise
pickup.
4. Reset and sequence the module, if code reappears,
replace the flame detector.
5. Reset and sequence the module, if code reappears,
consult factory.
1. Check Main Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, consult
factory.
1. Check Ignition terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, consult
factory.
1. Check Pilot Valve terminal wiring and correct any errors.
2. Reset and sequence the module. If fault persist, consult
factory.
Internal Fault
1. Reset Module.
2. If fault repeats, consult factory
Internal Fault.
1. Reset Module.
2. If fault repeats, consult factory.
1. Return to Configuration mode and recheck selected
parameters, re-verify and reset module.
2. If fault repeats, verify electrical grounding.
3. If fault repeats, consult factory.
105