Header sensor fault
95
Stack sensor fault
96
Outdoor sensor fault
97
Internal Fault: A2D mismatch.
98
Internal Fault: Exceeded VSNSR voltage
tolerance
99
Internal Fault: Exceeded 28V voltage tolerance
105
Flame detected out of sequence
106
Flame lost in MFEP
107
Flame lost early in Run
108
Flame lost in run
109
Ignition failed
110
Ignition failure occurred
111
Flame current lower than WEAK threshold
112
Pilot test flame Timeout
113
Flame circuit timeout
122
Light off rate proving failed
123
Purge rate proving failed
124
High fire switch OFF
125
High fire switch stuck ON
126
Low fire switch OFF
127
Low fire switch stuck ON
128
Fan speed failed during prepurge
129
Fan speed failed during preignition
130
Fan speed failed during ignition
131
Fan movement detected during
Standby
132
Fan speed failed during run
136
Interrupted Airflow Switch failed to
Close
137
ILK failed to close
149
Flame detected
150
Flame not detected
151
High fire switch ON
3. If previous steps are correct and fault persists, consult
factory.
1. Check wiring and correct any possible errors.
2. Replace the header sensor.
3. If previous steps are correct and fault persists, consult
factory.
1. Check wiring and correct any possible errors.
2. Replace the stack sensor.
3. If previous steps are correct and fault persists, consult
factory.
1. Check wiring and correct any possible errors.
2. Replace the outdoor sensor.
3. If previous steps are correct and fault persists, consult
factory.
Internal Fault.
1. Reset Module.
2. If fault repeats, consult factory.
1. Check that flame is not present in the combustion
chamber. Correct any errors.
2. Make sure the UV flame detector wires are protected from
stray noise pickup.
3. Reset and sequence the module, if code reappears,
replace the flame detector.
4. Reset and sequence the module, if code reappears,
consult factory.
1. Check pilot valve operation. Correct any errors.
2. Check the fuel supply.
3. Check fuel pressure and repeat Pilot tests.
4. Check pilot assembly ignition electrode and flame detector.
5. If steps 1 through 4 are correct and the fault persists,
consult factory.
Hold time of recycle and hold option. Will not be a lockout
fault. Hold Only.
Internal hardware test. Not a lockout.
Interrupted Pilot application and flame lost when system in
"test" mode.
1. Reset the module to restart.
Flame sensed during Initiate or off cycle, hold 240 seconds, if
present after 240 seconds, lockout.
1. Check wiring and correct any potential wiring errors.
2. Check VFDs ability to change speeds.
3. Change the VFD
4. If the fault persists, consult factory.
Internal Fault
1. Reset Module.
2. If fault repeats, consult factory
Internal Fault
1. Reset Module.
2. If fault repeats, consult factory
1. Check wiring and correct any potential wiring errors.
2. Check VFDs ability to change speeds.
3. Change the VFD
4. If the fault persists, consult factory.
Internal Fault
1. Reset Module.
2. If fault repeats, consult factory
1. Check wiring and correct any possible shorts.
2. Check Interlock (ILK) switches to assure proper function.
3. Verify voltage through the interlock string to the interlock
input with a voltmeter.
4. If steps 1-3 are correct and the fault persists, consult
factory.
1. Holds if flame detected during Safe Start check up to
Flame Establishing period.
1. Sequence returns to standby and restarts sequence at the
beginning of Purge after the HF switch opens. If flame
detected during Safe Start check up to Flame Establishing
period.
Internal Fault
1. Reset Module.
104
H
H
H
L
L
L
H or L
L
L
L
L
H
H
L
L
L
L
H
H
H
H