4-27 Frost Protection Configuration Parameters

Table 4.14 displays Frost Protection configuration parameters.
Refer to 5-9 FROST PROTECTION RELATED CONFIGURATION for Frost Protection parameter programming.
Parameter
CH frost protection enable
DHW frost protection enable
LL frost protection enable
Outdoor frost protection setpoint
LL frost protection rate
CH pump frost overrun time
DHW pump frost overrun time

4-28 DHW Storage Configuration Parameters

Table 4.15 displays DHW Storage configuration parameters.
Refer to 5-10 DHW STORAGE CONFIGURATION for DHW Storage parameter programming.
Parameter
DHW storage enable
Storage time
DHW storage setpoint
DHW storage on hysteresis
DHW storage off hysteresis

4-29 Warm Weather Shutdown Configuration Parameters

Table 4.16 displays Warm Weather Shutdown configuration parameters.
Refer to 5-11 WARM WEATHER SHUTDOWN CONFIGURATION for Warm Weather Shutdown parameter
programming.
Parameter
Enable
Setpoint
alert and holds while waiting for a delay to expire, and
after the delay it tries again.
Recycle & delay with limit: Same as above but with
retry limit. If limit count is reached lockout will occur.
Table 4.13 – Other Limit Configuration Parameters
Disabled or enable CH frost protection
The CH frost protection feature can be enabled to run
pumps and possibly fire the burner whenever the CH
input sensor is too cold.
Disabled or enable DHW frost protection
The DHW frost protection feature can be enabled to run
pumps and possibly fire the burner whenever the DHW
input sensor is too cold.
Disabled or enable LL frost protection.
No limit
Rate used when LL frost protection is active.
0-600 seconds (0 = Not configured)
0-600 seconds (0 = Not configured)
Table 4.14 – Frost Protection Configuration Parameters
Disabled or enable DHW Storage.
If it is disabled then the other DHW storage parameters
are ignored.
This parameter provides the DHW storage time. When
enabled and normal DHW call for heat is satisfied the
DHW storage demand will persist for this time interval. If
normal demand returns the timer is reset.
This parameter provides the setpoint used during DHW
storage demand.
Differential above setpoint when boiler is turned on
2 °F to 30 °F (1 °C to 16 °C)
Differential above setpoint when boiler is turned off
2 °F to 30 °F (1 °C to 16 °C)
Table 4.15 – DHW Storage Configuration Parameters
Disabled or enable WWSD.
Disable: WWSD is not active.
Shutdown after demand ended: Any current CH
demand that is present prevents WWSD from becoming
true. WWSD becomes true when CH demand is
satisfied.
Shutdown immediately: When WWSD becomes true, it
immediately cause CH demand to end.
Setpoint temperature at which activates WWSD.
Comment
Comment
Comment
60
Password
Installer
Installer
Installer
Installer
Installer
Installer
Installer
Password
Installer
Installer
Installer
Installer
Installer
Password
Installer
Installer
Rev 2.1