FX2N-32DP-IF Profibus-DP Interface Unit
7.

Diagnostic Message

7.1

Diagnostic Massage Frame

When a diagnostic error occurs in the 32DP-IF, a diagnostic message is sent form the 32DP-IF
to the DP-master as shown in Figure 7.1. Refer to section 4.2 for the diagnostic message
description.
Note:
If the DP-master receives a diagnostic message, make provisions for the system to act
safely in accordance with the error message.
Figure 7.1: Diagnostic Massage Frame
Byte No.
Total length of diag-
Description
nostic massage data
is 9 (09 Hex)
Byte No.
Second diagnostic
Description
Higher byte of D8004
Byte No.
Higher byte of last
diagnostic message
Description
data
*1 This diagnostic message is either number of momentary power failures or the error code
relating to the contents of D8004 (byte No. 3, 4). For error code, refer to section 4.2.4 or
8.3.3.
*2 This diagnostic message is either "0" or the contents of D8068.
7.2

Diagnostic Message Contents List

Table 7.1: Diagnostic Message List
Item
32DP-IF status is STOP
Momentary power failure
Power down
I/O bus error
Parameter error
Operation error
0
Lower byte of D8029
4
message
Lower byte of diag-
nostic
8
*2
This velure is "0".
This velure is number of momentary
power failures in D8007.
This velure is error code in D8061.
This velure is error code in D8064.
This velure is error code in D8067.
1
First diagnostic message
Higher byte of D8029 Lower byte of D8004
5
Third diagnostic message
Higher byte of error
*1
code
Third diagnostic message
Diagnostic Message 7
2
Second diagnostic
6
Lower byte of last
diagnostic message
data
*1
Last diagnostic message
This velure is "0".
This velure is in D8068.
3
message
7
*2
7-1