FX2N-32DP-IF Profibus-DP Interface Unit
2.2.2

Wiring for 32DP-IF and Profibus-DP Network

To connect the 32DP-IF to a Profibus-DP network use only the Profibus connectors and
shielded twisted-pair cable complying with EN50170.
Please use terminating resistors and Profibus connectors as shown in the DP-master manual
and Profibus connector manual.
The 32DP-IF does not have a terminating resistance built-in.
Figure 2.4: Wiring about 32DP-IF and Profibus-DP Network
For Profibus
connector, refer
to Figure 2.6.
Shielded twisted-pair
cable complying with
EN50170 to Profibus-
DP network
Grounding plate
Grounding
resistance of
100
or less
(Class 3)
Figure 2.5: Wiring for Power Line Circuit
Circuit protection device
100 ~ 240 V AC
Connect to "N" terminals
Figure 2.6: Profibus Connector
FX
-32DP-IF Profibus
2N
Interface-DP Unit
100 ~ 240 V AC
MC
MC
Shielded twisted-pair cable to
Profibus-DP network
Power line
Service supply
circuit
L
N
24+
COM
FX
-32DP-IF
2N
Profibus-DP
Interface Unit
For noise prevention please attach at least 50 mm
(1.97") of the twisted-pair cable along the grounding
plate to which the ground terminal is connected.
Emergency stop
Power supply
MC
for loads
Fuse
MC
Power supply
for loads
Connect to "L" terminals
Wiring and Mounting Arrangements 2
For power circuit,
refer to Figure 2.5.
2-3