Specifications; General Specifications; Power Supply Specifications - Mitsubishi FX2N User Manual

Profibus-dp interface unit
Hide thumbs Also See for FX2N:
Table of Contents

Advertisement

FX2N-32DP-IF Profibus-DP Interface Unit
3.

Specifications

3.1

General Specifications

Table 3.1: General Specifications
Item
Operating Temperature
Storage Temperature
Operating Humidity
Storage Humidity
Vibration Resistance
- Direct Mounting
Vibration Resistance
- DIN rail Mounting
Shock Resistance
Noise Immunity
Dielectric Withstand Voltage 1,500 V AC > 1 min, tested between all points, terminals and ground
Insulation Resistance
Grounding
Planned Certifications
3.2

Power Supply Specifications

Table 3.2: Power Supply Specifications
Item
Power Supply
Max. Allowable Momentary
Power Failure Period
Fuse (size) Rating
In-rush Current
Power Consumption
24 V DC Service Supply
Max. 5 V DC Bus Supply
0 to 55 °C (32 to 131 °F)
-20 to 70 °C (-4 to 158 °F)
35 to 85% Relative Humidity, No condensation
35 to 90% Relative Humidity, No condensation
Conforms to JIS C0040; 10 - 57 Hz: 0.75 mm Half Amplitude
57 - 150 Hz: 9.8 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Conforms to JIS C0040; 10 - 57 Hz: 0.035 mm Half Amplitude
57 - 150 Hz: 4.9 m/s
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Conforms to JIS C0041: 147m/s
3 times in each direction X, Y, and Z
1,000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
5 M > at 500 V DC, tested between all points, terminals and ground
Class 3 (Grounding resistance is 100
CE
100 ~ 240 V AC +10% -15%, 50/60 Hz
10 ms at 100 V AC
(< 10 ms, 32DP-IF = RUN continue, > 10 ms, 32DP-IF = power down)
3 A < 5
20 mm (0.2
100 V AC Max. 40 A < 5 ms, 200 V AC Max. 60 A < 5 ms
35 VA
500 mA
220 mA
Description
2
Acceleration
2
Acceleration
2
Acceleration, Action Time: 11 ms
or less)
Description
0.79 inches)>
Specifications 3