Preparation Of The Wall - Flavel FBFC**MN2 Installation, Maintenance & User Instructions

Calibre
Table of Contents

Advertisement

2.2.3
NOTE : WHEN MEASURING LENGTH BETWEEN FIREBOX AND
THE OUTER WALL TAKE INTO ACCOUNT THE DISTANCE
BETWEEN THE BACK OF THE FIREBOX AND THE INNER WALL AS
THIS WILL VARY BETWEEN INSTALLATIONS, DEPENDENT UPON
THE FIRE SURROUND REBATE OR CAVITY DEPTH. (DIMENSION
"X" BELOW - FIG. 5).
Fig. 5
300mm
2.2.4
The appliance must be fitted into a fireplace or false chimney
constructed of non-combustible materials, minimum width 410mm,
minimum height 555mm and minimum surround or false chimney breast
rebate 75mm.
2.3

PREPARATION OF THE WALL

2.3.1
The appliance and flue pipes must be installed at right angles to the
mounting wall. The appliance itself should be installed vertically against
a flat wall. Where an uneven wall surface is found, appropriate action
should be taken to ensure that the appliance is not stressed or does not
distort when installed.
Ensure that the floor surface onto which the appliance is mounted onto
is flat. The minimum height from the floor to the centre of the flue is
shown on fig. 6 overpage.
Flue Terminal
Cavity
X
405mm
485mm Including
Firebox Flanges
760mm
8
Outer Wall
Inner Wall
185mm

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fbfc**rn2Fbfc**en2Fbfc**mp2

Table of Contents