Camus Hydronics DRH300 Installation, Operation And Service Manual page 42

Gas fired commercial condensing stainless steel tube boilers
Table of Contents

Advertisement

Master Boiler, System Sensor
Description
Master boiler system sensor
configuration
Outdoor Sensor connected to Slave boiler 2 (DRH ONLY)
Description
Slave boiler outdoor sensor
configuration
When done correctly, the
outdoor temperature will be
shown on the Master boiler
36
Electrical Connection(s)
Electrical Connection(s)
Slave Boiler
Programming Instructions
1) Press
and
2) Press [Sensor Configuration]
3) Select S5 (J8-11) Sensor
4) Connector Type: 10K NTC Single Non-Safety
5) The control will proceed into a Lockout 2 condition
6) Press [Verify] > [Begin] > [Yes]
7) Press the reset button on the ignition control within the alotted time
Programming Instructions
1) Press
and
2) Press [Sensor Configuration]
3) Select S5 (J8-11) Sensor
4) Connector Type: 10K NTC Single Non-Safety
5) The control will proceed into a Lockout 2 condition
6) Press [Verify] > [Begin] > [Yes]