Camus Hydronics DRH300 Installation, Operation And Service Manual page 34

Gas fired commercial condensing stainless steel tube boilers
Table of Contents

Advertisement

Modulation: System Sensor, Outdoor Reset Operation (Standalone)
NOTE: Outdoor Reset Module (PN: W8735S1000) required.
Description
Boiler operates with variable
setpoint determined by
outdoor reset curve
Modulates on system sensor
Heat demand is generated
when Remote Operator is
closed.
28
Electrical Connection(s)
Programming Instructions
1) Connect Remote Operator
2) Connect System sensor to System/Outdoor
contacts
3) Connect Outdoor Sensor to J3 ECOM connector
4) Place both toggle switches in LOCAL
5) Press
and
6) Press Outdoor Reset Configuration
7) Press the
to arrive at Central Heat
8) Select Enable: Enable
9) Select Maximum outdoor temperature (WWSD)
10) Select Minimum outdoor temperature (Outdoor
Design)
11) Select Low Water Temperature (Min. Water
Temp.)
12) Select Outdoor boost maximum off point
(Design Max.)