4-20mA/ 2-10Vdc Firing Rate Operation (Standalone)
Description
Boiler operates with variable
setpoint determined by 4-
20mA incoming signal
Modulates on header sensor
Heat demand is generated
when Remote Operator is
closed and 4-20mA or 2-
10Vdc signal is present.
System Sensor Enable (Standalone)
Description
Method to enable system
sensor for Standalone
applications
30
Electrical Connection(s)
1) Place both toggle switches in LOCAL
2) Press
3) Press [Lead Lag Master Configuration]
4) Press [Advanced Settings >]
5) Press the
6) Select Modulation rate source = S2 (J8-6) 4-20mA and burner on/off
7) Place toggle switch to REMOTE for remote operation (if required)
Electrical Connection(s)
Programming Instructions
and
to arrive at Central Heat
Programming Instructions
1) Press
and
2) Press [Sensor Configuration]
3) Select S5 (J8-11) Sensor: 10K NTC Single Non-Safety
4) The control will proceed into a Lockout 2 condition
5) Press [Verify] > [Begin] > [Yes]
6) Press the reset button on the ignition control within the alotted time