Datasheet - Omnik Omniksol-1k-TL User Manual

Energy-solar inverters
Table of Contents

Advertisement

3.3 Datasheet

Omniksol-1k-TL
Type
Input (DC)
Max. PV-generator power
Max DC voltage
MPPT DC voltage range
Turn off DC Voltage
Max. DC current
Nominal DC current
Number of DC connection
DC-connection
Number of MPP trackers
Turn on power
Output (AC)
Max. AC Power
Nominal AC power
Max. AC current
Nominal AC current
Power connection
Grid voltage range
Grid frequency range
Power factor
Harmonic distortion (THD) at nominal output
AC Connector
Power consumption
Own consumption in operation
Power consumption at night
Power consumption at standby
Efficiency
Max. Efficiency (at 360VDC)
Euro efficiency (at 360VDC)
MPPT efficiency
Safety and protection
Internal overvoltage protection
DC Insulation monitoring
Earth fault protection
Grid monitoring
Earth fault current monitoring
DC current monitoring
Islanding protection
Normative reference
CE- compliant according to
10
P
[W]
pv
V
[V]
max(DC)
V
[V]
mppt
V
[V]
min(DC)
I
[A]
max(DC)
I
[A]
N(DC)
P
[W]
min(DC)
P
[V]
max(AC)
P
[W]
N(AC)
I
[A]
max(AC)
I
[A]
N(AC)
According to VDE 0126-1-1, RD1663, ENEL2010,C10/11,
According to VDE 0126-1-1, RD1663, ENEL2010,C10/11,
P
[W]
own(AC)
P
[W]
nig(AC)
P
[W]
std(AC)
According to VDE 0126-1-1, RD1663, ENEL2010,C10/11
According to VDE 0126-1-1, RD1663, ENEL2010,C10/11
According to VDE 0126-1-1, RD1663, ENEL2010,C10/11
According to VDE 0126-1-1, RD1663, G83/1, AS4777
EN 62109, EN 61000-6-1, EN 61000-6-3, EN 61000-6-2, EN
EN61000-3-2, EN61000-3-3, EN61000-3-12, EN61000-3-11
Omniksol-1k-TL
1300
500
80- 300
80
16
8.5
1
MC4
1
10
1100
1000
5.8
4.3
Single phase
G83/1 AS4777
G83/1, AS4777
0.99 (>30% of Full Load)
<2%
Plug-in connector
30
0
6
97.4%
96.6%
99.9%
Yes
Yes
Yes
G83/1, AS4777
G83/1, AS4777
G83/1, AS4777
61000-6-4