REMEHA Quinta 45 Technical Information page 54

Hide thumbs Also See for Quinta 45:
Table of Contents

Advertisement

0*
Setting failure
1!
Failure of inter-
nal communi-
cation bus
1@
External inter-
lock
1*
Flow tempera-
ture too high
1(
Return tempe-
rature too high
2$
Return temp >
flow temp
2*
Fan not run-
ning
2(
Fan runs con-
tinuously or
speed signal
not correct
3!
Temperature
sensor failure
3@
3$
3^
3&
4)
Setting failure
7&
Ionisation failu-
re during boiler
operation
- check parameter D (second digit must be 0)
- short circuit in flat cable: replace flat cable
- water/condensation on display
- possibly external EMC contamination
- The external interlock (terminals 10 and 14) open cir-
cuit : check external interlock or replace link between
terminals 10 and 14.
- Fuse F2 failed
Check:
- the waterflow, ref. Par. 7.4.7
- system for trapped air
- sensors for resistance at set temperature, see graph in
Fig. 22.
- if the boiler is full of water
- Flow sensor badly installed
- Pump operating in wrong direction or flow and return
connections crossed
- Fan or motor failed
- Supply and/or signal control cable – poor connections
or failed.
- Check control cable connections and for continuity
- Fan defective
- Flue draft conditions too high
Flow temperature sensor short circuit
Return temperature sensor short short circuit
Outside temperature sensor short short circuit
Flow temperature sensor not connected or open circuit
Return temperature sensor not connected or open circuit
check parameter D (first digit must be 0)
After 4 restarts during 1 heat demand
- flue gas recirculation (internal/external)
- insufficient air flow – check fan or air inlet/flue outlet for
obstruction
- incorrect combustion.