Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

5.
Select Configure, option 5, to configure the Power+ modules:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------
2> UPSs
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
6.
Select # UPSs (total), option 2, to specify the total number of modules in the system:
[Main Menu > SETUP > (password) > Ent > Service > Configure]
1> # OF UPSs (redundancy) 5> Dry, Alarms
2> # OF UPSs (total)
3> # OF BATT
4> Static Switch Setup
7.
Use the arrow keys to specify the total number of modules installed in the Power+, and then press
Ent:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (total)]
Set number of UPSs (total)
8.
Select 1, # of UPSs (Redundancy) in Figure 42 to specify the number of modules used for
redundancy:
[Main Menu > SETUP > (password) > Ent > Service > Configure > # OF UPSs (redundancy)]
Set number of UPSs (Redundancy)
Note: The redundant modules are designated to replace other system modules when they stop working.
For example, a 100-kVA system with 10 modules of which two are configured for redundancy can
deliver a maximum of 80 kVA.
42
G
E
AMATRONIC
LECTRONIC
4> DryOut Test 7> --------
5> Configure

Figure 41: Service menu

7> Parallel/StandAlone

Figure 42: Configure menu

04
(02

Figure 43: # of UPSs (Total)

01
(04 total)

Figure 44: # of UPSs (Redundancy)