Setting Upss; Testing Dry Output Relays; Figure 214: Setup Menu; Figure 215: Service Menu - Gamatronic POWER+ User Manual

Parallel multi-system configuration
Hide thumbs Also See for POWER+:
Table of Contents

Advertisement

2.
Select Service:
[Main Menu > SETUP > (password) > Ent]
1> Alarm set
2> Module conf. 6> Site
3> Battery
4> Charge
7.12.1

Setting UPSs

1.
Select UPSs:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------
2> UPSs
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
2.
Use the arrow keys to set UPSs, and press Esc when finished:
[Main Menu > SETUP > (password) > Ent > Service > UPSs]
1234
++++
SET UPSs
Enter =
7.12.2

Testing Dry Output Relays

1.
Select DryOut Test:
[Main Menu > SETUP > (password) > Ent > Service]
1> ------
2> UPSs
3> ------- 6> En/Dis shar 9> SC2012..
Select, then Enter
110
G
E
AMATRONIC
5> Time
7> Password #1
8> Service

Figure 214: Setup menu

4> DryOut Test 7> --------
5> Configure

Figure 215: Service menu

(UP= ON<+>, DOWN= OFF<->)
Execute

Figure 216: Set UPSs

4> DryOut Test 7> --------
5> Configure

Figure 217: Service menu

I
L
.
LECTRONIC
NDUSTRIES
TD
9> Silicon
8> Powr.Calib
Esc= Go back
8> Powr.Calib
POWER +
UPS,
,
PARALLEL
USER GUIDE
. 2.0
REL