Mechanical Specifications (Ups Cabinet Only); Environmental Specifications; Db15 Connector Pinouts And Designations; Ups Manager Dry Contact Interface - MGE UPS Systems 40-150kVA Installation And User Manual

Mge ups systems uninterruptible power supply installation and user manual 40-150kva
Table of Contents

Advertisement

Comet 40-150kVA
1.3.4

Mechanical Specifications (UPS Cabinet Only)

Height
Width
Depth
Weight at 480 VAC in and 480 VAC out
40/50kVA
880 lbs/400 kg
1.3.5

Environmental Specifications

Temperature
Operating:
Non-operating
and storage:
Humidity
Altitude
1.3.6

DB15 Connector Pinouts and Designations

The UPS Manager connector enables communication with the most common computer systems (AS/400,
NOVELL, etc.), or with the optional "UPS Manager UM1" software.
Table 1-2: UPS Manager Dry Contact Interface.
UPS Manager Dry Contact Interface (DB15)
Operation on Inverter
Operation on Bypass
Operation on Battery
Low Battery Shutdown Warning
UPS Remote Inverter Shutdown
Figure 1-9: Pinouts on the DB15 Connector.
PIJO PC board
Breaking
capacity of
contacts is:
P = 3va
V = 30VDC max.
I = 100mA max.
Please note that once the UPS remote inverter shutdown signal is applied, the Inverter stops and the
load transfers to bypass after a predetermined time (typically 2 minutes).
1 — 10
66.70 in/1694 mm
32.75 in/832 mm
33.42 in/823 mm
65/80kVA
100-150kVA
970 lbs/440 kg
1460 lbs/662 kg
0° C to 30° C (32° F to 86° F) continuous
15°C(60°F) to <25° C (<77° F) recommended
40° C (104° F) up to 8 hrs at 75% load
-30° C to 70° C (-22° F to 158° F)
0 to 95% non-condensing
<3000 ft. (1000m), up to 6000 ft. (<2000 m) @ 28° C (82°F) maximum
Softunor (DB9)
Diagnostics (for MGE Customer Care Center use only)
DB15 -pin
connector
5
Operation on Inverter
NO
8
NC
Operation on
NO
Bypass
NC
6
10
NO
Operation on Battery
9
NC
11
13
Low Battery Shutdown Warning
NO
7
NC
12
14
UPS Remote Inverter Shutdown
(3 to 15 VDC voltage signal)
4
GROUND
1
System Description and Specifications
8 7 6 5 4 3 2 1
15 14 13 12 11 10 9
86-160310-00 E00