5.3 Equipment Grounding Specifications

5.3.1 General Grounding Specifications
Table 5-16
Table 5-16 General grounding specifications
No.
1
2
3
4
5
5.3.2 Grounding Specifications for an Equipment Room
The grounding resistance of a comprehensive communication building should be less than or
equal to one ohm. The grounding resistance of an ordinary communication office should be less
than five ohms. The grounding resistance in an area where the earth resistance rate is high should
be less than 10 ohms.
5.3.3 Grounding Specifications for Devices
Table 5-17
Issue 02 (2014-12-05)
Improving the reliability of the AC power supply system reduces the necessary capacity of
storage batteries. For small offices, increase the capacity of storage batteries if it is difficult
to enhance the reliability of the AC power supply system.
The total capacity of the high-frequency switching rectifier must satisfy the power of the
communication loading and battery charging. If there are 10 or fewer active rectifier
modules, configure one backup module. If there are more than 10 active modules, configure
one backup module for every 10 active modules.
Install storage batteries in two or more groups. The capacity is determined by the duration
for which the storage batteries must supply power. For most offices, the batteries should
be able to supply power for at least one hour.
shows the general grounding specifications.
Description
The working grounding and protection grounding, including the shielded grounding
and the lightning-proof grounding of the cable distribution frame should share the
same grounding conductor.
The cable trays, shells, metal ventilation pipes, metal doors and windows in the
equipment room should be grounded for protection.
The metal parts of the equipment which are electrically floating in normal conditions
should be grounded for protection.
The ground cable must be connected securely to the protection ground bar of the
equipment room.
Do not use other equipment as part of the ground cable or electrical connection.
shows the equipment grounding specifications.