31c
Service parameters (10-199)
Circuit II (DHW)
Lines Setting ranges
24 Gear motor / thermo actuator
ON / OFF
30 Return temperature limitation
10 ... 110 °C
35 Return temperature influence
- max. limitation
-9.9 ... 0 ... 9.9
36 Return temperature influence
- min. limitation
-9.9 ... 0 ... 9.9
37 Time constant for return temperature
limitation
OFF / 1 ... 50
40 DHW pump post-run
0 ... 9 min.
41 DHW charging pump post-run (P3)
0 ... 9 min.
44 Max. DHW charging time
OFF / 1 ... 100 min.
45 DHW charging deactivation time
0 ... 250 min.
52 Compensation of heat loss in
circulation circuit
ON / OFF
55 Activation / deactivation of DHW
circulation during DHW charging
ON / OFF
78 Desired temperature for anti-bacteria
function
OFF / 1 ... 100 °C
80 Anti-bacteria function period
5 ... 250 min.
83 Internal relationship between circuits
I and II
0 ... 4
84 Pump P2 in DHW circuit, primary side
ON / OFF
85 Pump P2 in DHW circuit, primary side
ON / OFF
140 Function of temperature sensor S5
ON / OFF
141 Override input selection
OFF / 1 ... 6
147 Acceptable temperature deviation
below desired flow temperature
(ΔT1
ALARM
OFF / 1 ... 30 K
148 Acceptable temperature deviation
above the desired flow temperature
(ΔT2
ALARM
1 ... 30 K
149 Time interval Δt
activation of alarm function
1 ... 99 min.
174 Motor protection
OFF / 10 ... 59 min.
Factory settings
)
)
before
ALARM
Your settings
ON
60 °C
-2.0
0.0
25
0 min.
1 min.
OFF
0 min.
ON
OFF
OFF
120 min.
0
OFF
OFF
OFF
OFF
OFF
5 K
10 min.
OFF
°C
min.
min.
min.
min.
°C
min.
K
K
min.
min.