Service parameter(s) 141

141 Override input selection

Circuit
(I) / (II)
Choose an unused temperature sensor input for overriding the
schedule for circuit I and / or circuit II.
The override can be activated for comfort or setback mode.
For override the controller's mode must be in 'scheduled
operation'!
OFF: The controller's schedule is not overridden.
1 ... 6: Select an unused sensor input S1 ... S6 for
Connection example
If the override switch has gold-plated contacts, you can
choose one of the following solutions:
Closed switch:
Comfort temperature
Changeover switch:
Setback or comfort temperature
Connection example with ECA 9010
(used if the override switch does not have gold-plated
contacts).
16 - Brown
15 - Red
The ECA 9010 module is powered by the system device bus, which
means that the bus must be active. The bus is activated by setting
the controller address to 15 (line 199).
Setting range
OFF / 1 ... 6
the override of the circuit in question.
Closed switch:
Setback temperature
Green (S1 ... S6)
32s
Factory setting
(OFF) / (OFF)
The grey
side of the
ECL Card