Boost; Reference Ramping - Danfoss ECL COMFORT User Manual

Hide thumbs Also See for ECL COMFORT:
Table of Contents

Advertisement

32b
Service parameter(s) 12-13

12 Boost

Circuit
(I) / (II)
Shortens the heating-up period by increasing the desired flow
temperature by the percentage you set.
Set the percentage at which you want the desired
flow temperature increased temporarily.
In order to shorten the heating-up period after a setback
temperature period, the desired flow temperature can be
increased temporarily (max. 1 hour). At optimizing the boost
is active in the optimization period (line 14).
If a room temperature sensor or an ECA 60 / 61 / 62 / 63 is
connected, the boost stops when the room temperature has
been reached.
The boost also stops at the end of an optimizing period.

13 Reference ramping

Circuit
(I) / (II)
The time in which the desired flow temperature increases slowly
to avoid load peaks in the heat supply.
Set the ramping time for the controller.
Temperature °C
In order to avoid load peaks in the supply network, the flow
temperature can be set to increase slowly after a period with
setback temperature. This causes the valve to open slowly.
The grey
side of the
ECL Card
Setting range
0 ... 99%
Setting range
0 ... 99 min.
Setting line 13
Factory setting
(0) / (0)%
Factory setting
(0) / (0) min.
Time (min.)