Electrical Connections - 24 V A.c. - Danfoss ECL COMFORT User Manual

Hide thumbs Also See for ECL COMFORT:
Table of Contents

Advertisement

13a
Electrical connections -
24 V a.c. - in general
24 V a.c. connections - without safety thermostat
Establish these jumpers:
1-5-8-10-12-14
and jumper 2 to common N-terminal.
If an ECA 80 module is to be applied, the jumpers 14-26-29
must be established additionally.
24 V a.c. connections - with safety thermostat
This circuit diagram is only valid if Danfoss actuators are used
Establish these jumpers:
1-10-12-14
Safety thermostat:
4, 5 and 10 with ST- (safety thermostat)
and jumper 2 to common N-terminal.
If an ECA 80 module is to be applied, the jumpers 14-26-29
must be established additionally.
Optional
Optional

Advertisement

Table of Contents
loading

Table of Contents