Motor Protection; Lon Reset; Daylight Saving Time Changeover - Danfoss ECL COMFORT User Manual

Hide thumbs Also See for ECL COMFORT:
Table of Contents

Advertisement

Service parameter(s) 174-198

174 Motor protection

Circuit
(I) / (II)
Prevents the controller from unstable temperature control (and
resulting actuator oscillations). This can occur when there is
no DHW tapping, i.e. when the load is only due to the DHW
circulation, or when the heating demand in the heating circuit
is very low. The motor protection increases the lifetime of all
involved components.
OFF: Motor protection is not activated.
10 ... 59:
196 Service pin - LON
Circuit
I
This setting is only used in connection with LON communication
(see the documentation for the used communication unit).

197 LON reset

Circuit
I
This setting is only used in connection with LON communication
(see the documentation for the used communication unit).

198 Daylight saving time changeover

Circuit
I
Choose whether you want the change to summer / winter time to
be automatic or manual.
ON: The controller's built-in clock automatically
OFF: You change manually between summer and
Setting range
OFF / 10 ... 59 min.
Motor protection is activated after the set
activation delay.
A high value should be used for DHW
installations with many consumers.
Setting range
ON / OFF
Setting range
ON / OFF
Setting range
ON / OFF
changes + / - one hour on the standardized
days for daylight saving time changeover
for Central Europe.
winter time by setting the clock backward
or forward.
32x
Factory setting
(OFF) / (OFF)
Factory setting
OFF
Factory setting
ON
Factory setting
ON
The grey
side of the
ECL Card