Setting The Heat Curve (Circuit I); Storage Temperature (Circuit Ii) - Line C - Danfoss ECL COMFORT User Manual

Hide thumbs Also See for ECL COMFORT:
Table of Contents

Advertisement

20a

Setting the heat curve (circuit I),

storage temperature (circuit II) -
line C
C
Slope
Circuit
I
The symbol for the slope of the heat curve
will blink. Adjust the slope of the heat curve, if
required.
o
C
1.8
110
1.4
100
90
1.0
80
70
0.6
60
50
40
0.2
30
20
10
-30
How to determine another heat curve, if necessary:
Choose the calculated flow temperature for your system and
the determined min. outdoor temperature for your area.
Pick the heat curve closest to the crossing point of these two
values.
The setting of the desired room temperature has an influence
on the calculated flow temperature (heat curve), no matter if
a room temperature sensor is connected or not.
Floor heating systems
This controller is factory set for radiator systems, which typically
are high flow temperature systems.
To control floor heating systems, which typically are low flow
temperature systems, you need to change the heat curve
according to your type of system.
Slope
Circuit
I / (II)
The grey
side of the
ECL Card
1
1
2
2
ON
ON
1
8
Setting range
0.2 ... 3.4
2.2
2.6
3.0
3.4
-20
-10
Setting range
0.2 ... 3.4
3
ON
Slope
0
Displacement
0
10
Typical setting
Factory setting
1.8
o
C
20
1.0 / (1.0)

Advertisement

Table of Contents
loading

Table of Contents