Cut-in and cut-out temperature
at DHW charging - lines 1-2,
circuit II
The controller can control the DHW temperature with either
one or two tank temperature sensor(s). The controller will
automatically register the number of sensors.
1
Cut-out temperature difference - (lower sensor)*
Circuit
II
Set the difference between the desired charging temperature and
cut-out temperature (charging stop) .
Set the difference.
Example:
Desired charging temperature (section 3): 60 °C
Cut-out difference:
Calculated cut-out temperature (60-15) = 45 °C
2
Cut-in temperature difference - (upper sensor)*
Circuit
II
Set the difference between the desired charging temperature and
cut-in temperature (charging start).
Set the difference.
Example:
Desired charging temperature (section 3): 60 °C
Cut-in difference:
Calculated cut-in temperature (60-20) =
*
In case of two sensors.
The grey
side of the
ECL Card
Setting range
1 ... 99 K
Setting range
1 ... 99 K
Factory setting
15 K
Factory setting
20 K
40 °C
15 K
20 K