Quiet Operation (Heating); Powerful Mode Operation; Timer Control - Panasonic CS-E9RKUAW Service Manual

Hide thumbs Also See for CS-E9RKUAW:
Table of Contents

Advertisement

13.7

Quiet Operation (Heating)

Purpose
To provide quiet heating operation compare to normal operation.
o
Control condition
Quiet operation start condition
o
When "POWERFUL/QUIET" button at remote control is pressed.
Quiet LED illuminates.
Quiet operation stop condition
o
When one of the following conditions is satisfied, quiet operation stops:
Stop by OFF/ON button.
Timer "off" activates.
POWERFUL/QUIET button is pressed again.
When quiet operation is stopped, operation is shifted to normal operation with previous setting.
When fan speed is changed, quiet operation is shifted to quiet operation of the new fan speed.
When operation mode is changed, quiet operation is shifted to quiet operation of the new mode.
During quiet operation, if timer "on" activates, quiet operation maintains.
After off, when on back, quiet operation is not memorised.
Control contents
Fan speed auto
o
Indoor FM RPM depends on pipe temperature sensor of indoor heat exchanger. Auto fan speed is
changed from normal setting to quiet setting of respective fan speed. This is to reduce sound of Hi, Me,
Lo for 3dB.
Fan speed manual
o
Manual fan speed for quiet operation is -1 step from setting fan speed.
13.8

Powerful Mode Operation

When the powerful mode is selected, the internal setting temperature will shift lower up to 3.6°F (for Cooling/Soft
Dry) or higher up to 6.3°F (for Heating) than remote control setting temperature for 20 minutes to achieve the
setting temperature quickly.
13.9

Timer Control

13.9.1
ON Timer Control
ON Timer can be set using remote control, where the unit with timer set will start operation earlier than the setting
time. This is to provide a comfortable environment when reaching the set ON time.
60 minutes before the set ON time, indoor (at fan speed of Lo-) and outdoor fan motor start operation for 30
seconds to determine the indoor intake air temperature and outdoor air temperature in order to judge the
operation starting time.
From the above judgment, the decided operation will start operation earlier than the set time as shown below.
Indoor intake air
temperature (
86
77
13.9.2
OFF Timer Control
OFF Timer can be set using remote control, the unit with timer set will stop at set time.
o
F)
15 min
10 min
5 min
Outdoor air
o
86
95
(
F)
temperature (
Cooling/Soft Dry
Indoor intake air
o
temperature (
F)
59
41
35 min
o
F)
54
25 min
30 min
Outdoor air
o
32
41
(
F)
o
temperature (
Heating
F)