Panasonic CS-E9RKUAW Service Manual page 77

Hide thumbs Also See for CS-E9RKUAW:
Table of Contents

Advertisement

Diagnosis
Abnormality /
display
Protection control
H59
ECONAVI sensor
abnormality
H64
Outdoor high pressure
sensor abnormality
H97
Outdoor fan motor
mechanism lock
H98
Indoor high pressure
protection
H99
Indoor operating unit
freeze protection
F11
4-way valve switching
abnormality
F17
Indoor standby units
freezing abnormality
F90
Power factor correction
(PFC) circuit protection
F91
Refrigeration cycle
abnormality
F93
Compressor abnormal
revolution
F94
Compressor discharge
overshoot protection
F95
Outdoor cooling high
pressure protection
F96
Power transistor module
overheating protection
F97
Compressor
overheating protection
F98
Total running current
protection
F99
Outdoor direct current
(DC) peak detection
Note:
"○" – Frequency measured and fan speed fixed
The memory data of error code is erased when the power supply is cut off, or press the Auto Switch until "beep"
sound heard following by pressing the CHECK button at remote control.
Although operation forced to stop when abnormality detected, emergency operation is possible for certain errors
(refer to Error Code Table) by using remote control or Auto OFF/ON button at indoor unit. However, the remote
control signal receiving sound is changed from one "beep" to four "beep" sounds.
Abnormality
Protection
Judgement
operation
Continuous for
25s
Continuous for 1
minutes
2 times happen
within 30 minutes
4 times happen
within 30 minutes
3 times happen
within 40 minutes
4 times happen
within 10 minutes
2 times happen
within 20 minutes
4 times happen
within 20 minutes
4 times happen
within 30 minutes
4 times happen
within 20 minutes
4 times happen
within 30 minutes
3 times happen
within 30 minutes
3 times happen
within 20 minutes
Continuous
happen for 7 times
Problem
ECOANVI sensor open or
short circuit
High pressure sensor open
circuit during compressor
Outdoor fan motor lock or
feedback abnormal
Indoor high pressure
protection (Heating)
Indoor freeze protection
(Cooling)
4-way valve switching
abnormal
Wrong wiring and connecting
pipe, expansion valve
leakage, indoor heat
exchanger sensor open
circuit
Power factor correction
circuit abnormal
Refrigeration cycle abnormal
Compressor abnormal
revolution
Compressor discharge
pressure overshoot
Cooling high pressure
protection
Power transistor module
overheat
Compressor overheat
Total current protection
Power transistor module
current protection
77
Check location
• ECONAVI sensor (defective or
disconnected)
• ECONAVI PCB
• High pressure sensor
• Lead wire and connector
• Outdoor fan motor lead wire and
connector
• Fan motor lock or block
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
• Check indoor heat exchanger
• Air filter dirty
• Air circulation short circuit
• 4-way valve
• Lead wire and connector.
• Check indoor/outdoor connection
wire and pipe
• Indoor heat exchanger sensor
lead wire and connector
• Expansion valve lead wire and
connector.
• Outdoor PCB faulty
• Insufficient refrigerant or valve
close
• Power transistor module faulty or
compressor lock
• Check refrigeration system
• Check refrigeration system
• Outdoor air circuit
• PCB faulty
• Outdoor air circuit (fan motor)
• Insufficient refrigerant
• Check refrigeration system
• Power source or compressor lock
• Power transistor module faulty or
compressor lock